Solutions for your safety

Type: 3600 standard version
3900 low-resistance verson

Description

Single pole thermal-magnetic circuit breaker with tease-free, trip-free, snap action mechanism and two button operation (M-type TM CBE to EN 60934). Designed for plug-in mounting with E-T-A sockets 17-P10-Si, 23-P10-Si, 63-P10-Si; or panel mounting using E-T-A clips. Featuring an unprotected shunt tap terminal and optional auxiliary contacts. Type 3900 offers lower internal resistance values and is fitted as standard with auxiliary contacts and an intermediate reset position in which all contacts are isolated.

Approved to CBE standard EN 60934 (IEC 60934).

Technical Data

Voltage rating
  • AC 240 V (50/60 Hz)
  • DC 65 V
  • UL/CSA: DC 80 V
Current ratings from 0.05 A until 16 A  type 3600
from 0.05 A until 10 A  type 3900
Number of poles single pole
Mounting method socket
Terminal design blade terminals
Actuation manual release
push button
Auxiliary contacts with auxiliary contacts
without auxiliary contacts
Water splash protection without water splash protection
Illumination without illumination
Typical life 5,000 operations at 2 x IN, resistive

5,000 operations at 1 x IN, inductive
Interrupting capacity Icn 3600:

0.05...0.8 A: self-limiting

1...2 A: 200 A

2.5...16 A: 400 A

3900:

0.05...0.2 A: self-limiting

0.3...2 A: 200 A

2.5...10 A: 400 A
Certificates VDE, CSA, UL

Accessories

Accessories

Order number Description
17plus power distribution system
17-P10-Si/-20025 sockets
17-P70-Si/-20025 sockets
23-P10-Si socket
63-P10-Si socket
X 200 409 01 adapter for socket 16 for track mounting
X 210 588 01-04 Connector bus links -P10
01 = 1.5 mm2 brown
02 = 2.5 mm2 black
03 = 2.5 mm2 red
04 = 2.5 mm2 blue
X 211 157 01/02 busbar for mounting socket
01 = with terminal
02 = without terminal
Y 300 504 02 mounting clip
Y 300 581 03 retaining clip for socket
Y 300 581 11 retaining clip for socket
Y 301 398 02 extraction tool
Y 303 824 01 insulation sleeving for busbar

Applications

Applications

  • Automation
  • Automation & Process Control
  • Chemical, Oil & Gas
  • Minus DC 28 V
  • Minus DC 48 V
  • Minus DC 72 V
  • Pharmaceutical & Food
  • Power Engineering AC 240 V
  • Power Engineering DC 24 V
  • Telecom & Datacom

Downloads

Data sheet 303.8 KB